Test objective
The objective of this test is to compare the energy consumption of the Olimpia Splendid – Unico console unit to a conventional unit of the same size.
The Olimpia Splendid is an inverter driven compressor heat pump / cooling unit, whereas the conventional unit is an electric air heater / compressor cooling unit.
Test items
|
Manufacturer |
Type |
Cooling output |
Heating output |
|
Olimpia Splendid - Unico H12 |
DC Inverter driven heat pump / |
2.214 kW |
1.075 kW |
|
Traditional Unit |
Conventional Electric heating / compression cooling |
2.214 kW |
1.075 kW |
Test description
The test took place in 2 empty offices at Constantia business park of Growthpoint properties.
The rooms were located on the ground floor, located directly next to each other with the windows facing north. All remaining walls were inside walls.
Both rooms were of similar size, however the room with the Olimpia Splendid – Unico unit was slightly larger.
Additionally it needs to be mentioned, that the window surface of the room with the Olipmpia Splendid– Unico unit was more than double as large and the room received about an hour more direct sunlight during the day, since a staircase was blocking the sunlight to the room with the TRADITIONAL UNITunit earlier in the afternoon.
Room specifications
|
ROOM 1 (Traditional Unit) – room volume: |
33.78 m³ |
|
ROOM1 (Traditional unit) - window surface area: |
1.95 m² |
|
ROOM 2(Olimpia Splendid) – Unico – room volume: |
34.73 m³ |
|
ROOM 2 (Olimpia Splendid) – Unico- window surface area: |
4.52 m² |
Test details